Location : Main > Our Products > Electrical Steel > Grain-Oriented Electrical Steel

















1. PG-Core

The grain's easy magnetization direction is aligned to the rolling direction. Therefore, this product features excellent magnetic properties in the rolling direction. It is widely used for large-sized power transformers or large or small size transformers.

Standard Sizes

Classification
Grade
Thickness
(mm)
Width(mm)
Inner Coil Diameter
(mm)
Available Width Range
Standard Width
PG-Core
27PG110
27PG120
27PG130
0.27
850-1000
1000
508-520
(Standard:508)
30PG110
30PG120
30PG130
30PG140
0.30
35PG145
35PG155
0.35

Notice: For non-standard sizes, please contact us.

Surface Insulation

C-10 coating (ASTM C5 ) is applied.

Specification

Magnetic properties and lamination factor
Grade
Thickness
(mm)
Density
(g/cm³)
Core Loss w/kg
(w17/50)
Induction T
(B8)
Lamination Factor
(%)
27PG110
27PG120
27PG130
0.27
7.65
1.10 and under
1.20 and under
1.30 and under
1.80 and over
95.0 and over
30PG110
30PG120
30PG130
30PG140
0.30
1.10 and under
1.20 and under
1.30 and under
1.40 and under
1.80 and over
95.5 and over
35PG145
35PG155
0.35
1.45 and under
1.55 and under
1.80 and over
96.0 and over
 

Notice: the above test is conducted in accordance to IEC 60404-2 (or JIS C 2550-2000). Core loss and induction are measured after stress relief annealing in a longitudinal direction.

Dimension Range

Width
(mm)
Thickness
(mm)
Thickness tolerance
(mm)
Camberness
(mm)
Width Tolerance
(mm)
Linear Measure
(Standard 2m )
(mm)
850 and over
0.27
0.30
0.35
±0.03
0.03 and under
+0.6
-0
1.0 and under

(Notice: Camberness tolerance means the difference between the thickness at the center and 15mm from the edge.

Typical Electrical and Magnetic Property

Grade
Thickness
(mm)
Density
(g/cm³)
Resistivity
(-cm)
Core Loss (w/kg)
Induction
(B8)
W15/50
W17/50
w15/60
W17/60
27PG110
27PG120
27PG130
0.27
7.65
48
0.76
0.78
0.82
1.05
1.15
1.22
1.01
1.02
1.07
1.37
1.48
1.55
1.85
1.85
1.84
30PG110
30PG120
30PG130
30PG140
0.30
0.80
0.83
0.87
0.90
1.08
1.17
1.25
1.32
1.05
1.09
1.12
1.17
1.48
1.53
1.61
1.70
1.85
1.85
1.84
1.84
35PG145
35PG155
0.35
0.98
1.01
1.37
1.45
1.29
1.33
1.80
1.89
1.84
1.83

Notice: Above figures are not guaranteed. Above test is conducted in accordance to IEC 60404-2 or JIS C 2550-2000, using specimens taken longitudinal to the rolling direction and then annealed to enhance magnetic properties.

Typical Mechanical Property and Lamination Factor

Thickness
(mm)
Tensile Strength
(N/m²)
Yield Point
(N/m²)
Elongation
(%)
Angle
(%)
Lamination Factor
(%)
L
C
L
C
L
C
0.27
0.30
0.35
344
355
364
385
395
423
322
330
345
340
350
357
10
10
10
36
38
40
180
180
180
98.0
98.0
98.5

Notice: Above test is conducted in accordance to IEC 60404-2 or JIS C 2550-2000. L means specimens taken longitudinal to the rolling direction, C means specimens taken at a right angle to the rolling direction Specimens with C-10 coating are used for lamination factor tests.

2. PH-Core

The directional property of grain-oriented electrical steel is more reinforced in the rolling direction than PG-Core and therefore features low core loss and high induction. It is used for iron cores of both large and other size power transformers and it is efficient and useful for size reduction of machinery.

Standard Sizes

Proudct
Grade
Thickness
(mm)
Width(mm)
Inner Coil Diameter
(mm)
Available Width
Standard Width
PH-Core
23PHD080
23PHD085
23PH090
23PH095
23PH100

0.23
850-1000
1000
(PHD : 950)
508-520
(standard:508)
27PHD090
27PHD095
27PH095
27PH100
0.27
30PH100
30PH105
0.30
35PH115
35PH125
35PH135
0.35

Notice: For non-standard width, please contact us.
PHD is magnetic domain refined product treated by Laser-irradiation.

Surface Coating

C-10 coating (ASTM C5 ) is applied.

Specifications

Magnetic properties and lamination factors
Grade
Thickness
(mm)
Density
(g/cm³)
Core Loss W/kg
(W17/50)
Induction T
(B8)
Lamination factor
(%)
23PHD080
23PHD085
23PH090
23PH095
23PH100
0.23
7.65
0.80 and under
0.85 and under
0.90 and under
0.95 and under
1.00 and under
1.88 and over
94.5 and over
27PHD090
27PHD095
27PH095
27PH100
0.27
0.90 and under
0.95 and under
0.95 and under
1.00 and under
1.88 and over
95.0 and over
30PH100
30PH105
0.30
1.00 and under
1.05 and under
1.88 and over
95.5 and over
35PH115
35PH125
35PH135
0.35
1.15 and under
1.25 and under
1.35 and under
1.88 and over
96.0 and over

Notice: Above test is conducted in accordance with IEC 60404-2 or JIS C 2550-2000 methods, using specimens taken longitudinal to the rolling direction and then annealed to enhance magnetic properties. . PHD is tested by SST

Tolerance

Width
(mm)
Thickness
(mm)
Thickness Tolerance
(mm)
Camberness
(mm)
Width Tolerance
(mm)
Linear measure
(Standard 2m)
(mm)
850 and over
0.23
0.27
0.30
0.35
±0.03
0.03 and under
+0.6
-0
1.0and under

Notice: Camberness tolerance means the difference between the thickness at the center and 15mm from the edge.

Typical Electrical and Magnetic Properties

Grade
Thickness
(mm)
Density
(g/cm³)
Resistivity
(-cm)
Core Loss(w/kg)
Induction T
(B8)
W15/50
W17/50
w15/60
W17/60
23PHD080
23PHD085
23PH090
23PH095
23PH100
0.23
7.65
48
0.57
0.59
0.64
0.65
0.70
0.77
0.80
0.88
0.90
0.95
0.75
0.78
0.85
0.86
0.92
1.01
1.05
1.15
1.17
1.26
1.91
1.91
1.91
1.91
1.90
27PHD090
27PHD095
27PH095
27PH100
0.27
0.64
0.66
0.70
0.72
0.87
0.91
0.93
0.97
0.85
0.86
0.92
0.95
1.14
1.18
1.23
1.27
1.91
1.91
1.91
1.90
30PH100
30PH105
0.30
0.74
0.76
0.99
1.01
0.98
1.00
1.29
1.33
1.91
1.90
35PH115
35PH125
35PH135
0.35
0.87
0.93
0.96
1.14
1.22
1.26
1.15
1.20
1.26
1.53
1.60
1.69
1.91
1.90
1.90

Notice: The above test is conducted in accordance to the IEC 60404-2 or JIS C 2550-2000 methods, using specimens taken longitudinal to the rolling direction and then annealed to develop full magnetic properties
PHD is tested by SST

Typical Mechanical Property and Lamination Factor

Thickness
(mm)
Tensile Strength
(N/m²)
Yield Point
(N/m²)
Elongation
(%)
Hardness
(%)
Lamination Factor
(%)
L
C
L
C
L
C
0.23
0.27
0.30
0.35
381
370
353
353
442
412
400
400
356
337
330
330
383
367
358
358
7
7
8
8
38
38
40
40
195
195
185
185
97.5
97.5
98.0
98.0
 

Notice: The above test is conducted in accordance IEC60404-2 or JIS C 2550-2000. L means specimens taken longitudinal to the rolling direction, C means specimens taken at a right angle to the rolling direction. Specimens with C-10 coating are used for lamination factor tests.

 Copyright © POSCO, All rights reserved. Contact steelinfo@Steel-N.com for more information